ConstructCheck · Independent Building Consultancy & Compliance
Damp & Mould Survey Report
Registered Building Inspector · Level 3 Fire Door Inspector · CSCS Black Card · 25 years in construction
WhatsApp / Tel: 07507 246883 · info@constructcheck.com · constructcheck.com
Report Details
| Item | Detail |
|---|---|
| Report reference | CC-DM-0001 (Sample) |
| Property | 2-bed ground floor flat, [Address redacted], London |
| Client | [Client redacted], Housing Association |
| Inspection type | Damp, mould & condensation root-cause survey |
| Weather | Overcast, 8 °C, light rain in previous 48 hours |
| Inspector | Sebastian C, Registered Building Inspector |
| Occupancy | Occupied, tenant present |
1. Executive Summary
Significant black mould growth was found in the main bedroom and bathroom. The primary cause is condensation, driven by inadequate extraction and a thermal bridge at the bedroom external wall corner. A secondary penetrating damp defect was found below the kitchen window from a failed external sill joint.
| Ref | Location | Defect | Severity | Priority | Photo |
|---|---|---|---|---|---|
| DM-01 | Bedroom 1, NE corner | Condensation mould, thermal bridge | Major | Within 5 working days | Photo 1 |
| DM-02 | Bathroom | Extractor fan failed / undersized | Major | Within 5 working days | Photo 2 |
| DM-03 | Kitchen, below window | Penetrating damp, failed sill seal | Moderate | Within 28 days | Photo 3 |
| DM-04 | Whole property | Trickle vents closed / blocked | Minor | Advise tenant & landlord | Photo 4 |
2. Findings
Condensation Mould at External Corner
Observation: Black mould approx. 1.2 m² at ceiling-to-wall junction, north-east corner, extending behind wardrobe.
Readings: Surface temperature 9.1 °C vs room 18.4 °C. Relative humidity 74%. Dew point 13.7 °C, so the surface sits below dew point. Moisture meter readings at plaster surface only; deeper readings dry.
Thermal imaging: Cold band along ceiling junction consistent with missing or slumped insulation (thermal bridge).
Root cause: Condensation on a cold surface, worsened by restricted airflow behind furniture.
Recommendation: Mould wash with fungicidal treatment; inspect and make good loft or cavity insulation at junction; apply anti-condensation paint after drying; advise wardrobe set 50 mm off external wall.

Inadequate Extraction
Observation: Mould to ceiling and silicone around bath. Extractor fan not running on test.
Readings: RH 88% 20 minutes after shower use. Fan extract rate: nil.
Root cause: Failed extractor; moisture not removed at source.
Recommendation: Replace with humidistat-controlled fan, minimum 15 l/s, with overrun timer. Clean and treat mould; reseal bath.

Penetrating Damp Below Window
Observation: Tide-marked staining and blown plaster below window, approx. 600 mm wide.
Readings: High moisture readings confined to area directly below sill; readings drop to dry within 300 mm either side and at skirting level, ruling out rising damp.
External check: Open joint and cracked mastic at sill-to-frame junction; no drip groove clearance.
Root cause: Rainwater entering at failed sill joint.
Recommendation: Rake out and reseal sill joint, clear drip groove; allow wall to dry, then replaster with breathable lime-based plaster.

3. Hazard Assessment (HHSRS)
Damp and mould growth assessed as a Category 1 hazard, given active mould in a bedroom and bathroom, an occupied home and likely health impact. Under Awaab’s Law timescales for social landlords, works to make the home safe should be completed within 5 working days of this investigation.
4. Recommended Works Schedule
| Priority | Works | Ref |
|---|---|---|
| Urgent (5 working days) | Replace bathroom extractor; mould wash and treat bedroom and bathroom | DM-01, DM-02 |
| Short term (28 days) | Reseal kitchen sill; investigate and make good insulation at bedroom corner | DM-01, DM-03 |
| Follow-up | Replaster kitchen area once dry; re-inspect after 6–8 weeks | DM-03 |
| Advice | Open trickle vents; tenant ventilation guidance | DM-04 |
5. Methodology & Equipment
Visual inspection internally and externally; pin and capacitance moisture meters; thermo-hygrometer for temperature, RH and dew point; thermal imaging camera; extractor flow test. Readings taken at multiple heights to distinguish condensation, penetrating and rising damp.
6. Limitations
Non-invasive survey. Areas behind fixed furniture, floor coverings and sealed voids were not opened up. Findings reflect conditions on the inspection date.
7. Independence Statement
ConstructCheck is fully independent. We do not carry out remedial works or sell damp-proofing products, so our recommendations are based only on the evidence found.
Photo Appendix
Each photo is numbered and matched to its finding reference. Photos in this sample are illustrative.

View finding DM-01 ↑

View finding DM-02 ↑

View finding DM-03 ↑

View finding DM-04 ↑